Ultra Electronics, Nuclear Sensors & Process Instrumentation
- PO Box 300
- Round Rock, TX 78680-0300
- Tel. Toll Free: 800-880-9333
- Tel.: 512-434-2800
Ultra Electronics, Nuclear Sensors & Process Instrumentation is a business name of Weed Instrument Co., Inc.
|
Industrial Ethernet Fiber Optic Networking:
- Simple like unmanaged, but features like managed switch
- Ethernet compliancy IEEE 802.3, 802.3u, 802.3x, 802.3z, 802.1p and more
- Supports Traffic Prioritization IEEE 802.1p, Q0S, CoS, ToS for real time data transfer
- Port mirroring for mapping messages between ports
- Message rate filtering (broadcast storm protection) to prevent network downtime
- Ultra Electronics, NSPI Compact Enclosure (45mm wide), DIN-rail mount
- Two SC or ST 100BaseF (multimode and single mode) fiber optic ports
- Two RJ-45 copper Ethernet ports 10/100Mbps
- Removable, pluggable terminal strips
- Non-Blocking, Full Wire Speed Transmission
- Software configurable
Industrial Ethernet Self-Healing Ring Topology:
- Redundant self-healing ring operation
- Ultra Fast Link Loss Recovery Time (< 30ms + 5ms/hop)
- No IP Address and no master switch selection required
- Ring operation for up to 50+ switches
- PROTOCOL INDEPENDENT
Automatic (Plug ‘N Play Operation):
- Auto-crossover RJ45 MDI/MDIX
- Automatic Address Learning
- Automatic Master Switch selection
- Auto-sensing Full or half duplex
- Automatic and dynamic Buffer allocation per port
- Pre-configured for Ring operation
- Automatic Power Saving
- Auto-negotiating 10BaseT, 100BaseT
- Auto-polarity
Expandable and Scalable:
- Expandable and scalable ports through integrated backplane
- Store and forward mode
- 3.2 Gbps Memory bandwidth for full wire speed on all ports
- Flow control for half or full duplex
- MAC address aging after 300s
Alarm Diagnostics:
- Power and Switch status LED indicator
- Global Ring Status Alarm LED indicator
- Global (OK) Relay Alarm Contacts
- Local Relay (A1 & A2) Alarm Contacts
- Remote status monitoring using Modbus over Ethernet (UDP)
- Backplane port activity Status LED indicator
- Port Status ACT and LINK LED’s combined into one LED per port
Designed for Industrial Environments:
- FM (US & Canada) Class1, Div. 2 hazardous area certification
- -40 to +85° C operating temperature range
- 15-40 VDC power input via screw terminals
- Redundant power available via backplane (120/240VAC)
- Supports long distances between drops, 2 km (MM), 15, 40, 60 km (SM)
- CE FCC part 15, ICES-003, EN55022 EMI emissions
- 1500 VRMS 1 minute Ethernet isolation
- 15,000 watts peak Transient protection
- UL 94V-0 Packaging
|
|